VECS Lead Testing Results
Summary of Samples Collected at Victor Early Childhood School:
|
Building Name |
Date of Sampling |
Total Samples |
At or Below Action Level* |
Above Action Level* |
|
|
|
|
|
|
|
Victor Early Childhood |
June 3, 2025 |
182 |
164 |
18 |
|
|
|
|
|
|
*NYS Action Level is 5 parts per billion
Listing of Outlets Requiring Remediation
The following outlets were analyzed above the NYS Action Level:
|
Sample # |
Location |
Fixture/Outlet type |
Laboratory Analysis (in ppb) |
|
203.4-06 |
Boys Lav by elevator right |
Sink |
6.9 |
|
203.4-10 |
Girls Lav by 208 Left |
Sink |
5.1 |
|
203.4-11 |
Girls Lav by 208 Right |
Sink |
6.4 |
|
203.4-13 |
Room 208 |
Drinking Fountain |
5.0 |
|
203.4-18 |
Room 218 |
Sink |
8.4 |
|
203.4-19 |
Room 218 |
Drinking Fountain |
9.4 |
|
203.4-58 |
Room 013 Main |
Sink |
10.4 |
|
203.4-59 |
Room 013 Fac Lav |
Sink |
7.8 |
|
203.4-81 |
Kitchen 3 Bay Left |
Sink |
23.1 |
|
203.4-86 |
Kitchen Dishwash Handwash |
Sink |
9.7 |
|
203.4-88 |
PT Room 122/123 |
Sink |
5.6 |
|
203.4-89A |
DF Across from Gym |
Drinking Fountain |
14.1 |
|
203.4-89B |
DF Across from Gym |
Bottle Fill |
23.3 |
|
203.4-91 |
119 Lav |
Sink |
12.5 |
|
203.4-92 |
Room 118 |
Sink |
5.5 |
|
203.4-104 |
129 Rear Room |
Sink |
6.2 |
|
203.4-119 |
Girls Lav by 101 Left |
Sink |
6.6 |
|
203.4-158 |
Mens Lav Main Entrance |
Sink |
8.8 |