Skip To Main Content

VECS Lead Testing Results

Summary of Samples Collected at Victor Early Childhood School:

Building Name

Date of Sampling

Total

Samples

At or Below Action Level*

Above  Action Level* 

 

 

 

 

 

Victor Early Childhood

June 3, 2025

182

164

18

 

 

 

 

 

*NYS Action Level is 5 parts per billion
 

Listing of Outlets Requiring Remediation

The following outlets were analyzed above the NYS Action Level:

 

Sample #

Location

Fixture/Outlet type

Laboratory

Analysis 

(in ppb)

203.4-06

Boys Lav by elevator right

Sink

6.9

203.4-10

Girls Lav by 208 Left

Sink

5.1

203.4-11

Girls Lav by 208 Right

Sink

6.4

203.4-13

Room 208

Drinking Fountain

5.0

203.4-18

Room 218

Sink

8.4

203.4-19

Room 218

Drinking Fountain

9.4

203.4-58

Room 013 Main

Sink

10.4

203.4-59

Room 013 Fac Lav

Sink

7.8

203.4-81

Kitchen 3 Bay Left

Sink

23.1

203.4-86

Kitchen Dishwash Handwash

Sink

9.7

203.4-88

PT Room 122/123

Sink

5.6

203.4-89A

DF Across from Gym

Drinking Fountain

14.1

203.4-89B

DF Across from Gym

Bottle Fill

23.3

203.4-91

119 Lav

Sink

12.5

203.4-92

Room 118

Sink

5.5

203.4-104

129 Rear Room

Sink

6.2

203.4-119

Girls Lav by 101 Left

Sink

6.6

203.4-158

Mens Lav Main Entrance

Sink

8.8