VPS Lead Testing Results
Summary of Samples Collected at Victor Primary School:
|
Building Name |
Date of Sampling |
Total Samples |
At or Below Action Level* |
Above Action Level* |
|
|
|
|
|
|
|
Victor Primary |
June 3, 2025 |
174 |
141 |
33 |
|
|
|
|
|
|
*NYS Action Level is 5 parts per billion
Listing of Outlets Requiring Remediation
The following outlets were analyzed above the NYS Action Level:
|
Sample # |
Location |
Fixture/Outlet type |
Laboratory Analysis (in ppb) |
|
172.3-23 |
129 Women’s Fac Left |
Sink |
5.1 |
|
172.3-17 |
Room 131 Lav |
Sink |
5.9 |
|
172.3-15 |
Room 138 |
Drinking Fountain |
6.4 |
|
172.3-16 |
Room 136 |
Sink |
6.5 |
|
172.3-18 |
Room 131 Lav |
Sink |
7.5 |
|
172.3-30 |
Room 128 |
Sink |
7.5 |
|
172.3-9 |
Kitchen Combitherm Sprayer Right |
Sink |
8.0 |
|
172.3-25 |
Room 134 |
Sink |
9.1 |
|
172.3-14 |
Room 138 |
Sink |
11.7 |
|
172.3-27 |
Room 132 |
Sink |
12.0 |
|
172.3-29 |
Room 130 |
Sink |
12.6 |
|
172.3-35 |
Kiln Room |
Sink |
13.4 |
|
172.3-34 |
Room 125 Rear |
Sink |
14.0 |
|
172.3-28 |
Room 132 |
Drinking Fountain |
39.1 |
|
172.3-37 |
Room 123 |
Drinking Fountain |
14.2 |
|
172.3-62 |
Room 113 |
Drinking Fountain |
5.5 |
|
172.3-86 |
Room 107 |
Drinking Fountain |
5.0 |
|
172.3-87 |
Room 143 |
Drinking Fountain |
10.3 |
|
172.3-125 |
Room 168 |
Sink |
5.8 |
|
172.3-133 |
Room 164 |
Sink |
5.1 |
|
172.3-134 |
Room 161 |
Sink |
9.9 |
|
172.3-135 |
Room 161 |
Drinking Fountain |
14.5 |
|
172.3-141 |
Room 160 |
Drinking Fountain |
5.0 |
|
172.3-142 |
Room 157 |
Sink |
6.1 |
|
172.3-145 |
Room 158 |
Sink |
8.3 |
|
172.3-146 |
Room 158 |
Drinking Fountain |
12.1 |
|
172.3-148 |
Room 201 |
Sink |
11.2 |
|
172.3-149 |
Room 156 |
Sink |
5.0 |
|
172.3-151 |
Room 156 Lav |
Sink |
5.6 |
|
172.3-157 |
Girls Lav Center Left |
Sink |
8.1 |
|
172.3-158 |
Girls Lav Center Right |
Sink |
8.0 |
|
172.3-159 |
Girls Lav 2nd Right |
Sink |
6.7 |
|
172.3-174 |
Room 153 Lav |
Sink |
8.2 |